Features: • Excellent response to fast rising transients.• Ultra low capacitance.• 10KA surge capability tested with 8/20µs pulse as defined by IEC 61000-4-5• 10,000 A single shot surge capability tested with 8/20µs pulse as defined by IEC 61000-4-5Application...
SL1011B: Features: • Excellent response to fast rising transients.• Ultra low capacitance.• 10KA surge capability tested with 8/20µs pulse as defined by IEC 61000-4-5• 10,000 A ...
SeekIC Buyer Protection PLUS - newly updated for 2013!
268 Transactions
All payment methods are secure and covered by SeekIC Buyer Protection PLUS.
Part Number |
DC Voltage(V) |
DC Breakover Voltage Min-Max7 @ 100V/sec (V) |
Max Dynamic Breakover Voltage @ 100/µs (V) |
Alternating Discharge Current1,3 (A) |
Max Repetitive Impulse Discharge Current (kA) |
Max Single Impulse Discharge Current (kA) |
Max Single Impulse Discharge Current 10/350µs5,2 (kA) |
SL1011B230 |
230 |
184-276 |
375 |
10 |
10 |
20 |
2.5 |
SL1011B250 |
250 |
200-300 |
400 |
10 |
10 |
20 |
2.5 |
SL1011B260 |
260 |
210-310 |
420 |
10 |
10 |
20 |
2.5 |
SL1011B350 |
350 |
280-420 |
500 |
10 |
10 |
20 |
2.5 |
SL1011B500 |
500 |
400-500 |
750 |
10 |
10 |
20 |
2.5 |
SL1011B600 |
600 |
480-720 |
450 |
10 |
10 |
20 |
2.5 |
The SL1011B series offers high levels of performance on fast rising transients in the domain of 100V/µS to 1KV/µS, which are those most likely from induced Lightning disturbances. The SL1011B series also features ultra low capacitance (typically 1pF or less) making them ideal for the protection of high-speed transmission equipment. These devices are extremely robust and are able to divert a 10,000A pulse without destruction.