PWB02

Features: • TRMS active power relays for three phase balanced applications• Measuring if active power is within set limits• Measuring voltage on own power supply• Measuring ranges: 5A, 10A, MI current transformers• Power ON delay 1 to 30 s knob selectable• Separ...

product image

PWB02 Picture
SeekIC No. : 004467346 Detail

PWB02: Features: • TRMS active power relays for three phase balanced applications• Measuring if active power is within set limits• Measuring voltage on own power supply• Measuring r...

floor Price/Ceiling Price

Part Number:
PWB02
Supply Ability:
5000

Price Break

  • Qty
  • 1~5000
  • Unit Price
  • Negotiable
  • Processing time
  • 15 Days
Total Cost: $ 0.00

SeekIC Buyer Protection PLUS - newly updated for 2013!

  • Escrow Protection.
  • Guaranteed refunds.
  • Secure payments.
  • Learn more >>

Month Sales

268 Transactions

Rating

evaluate  (4.8 stars)

Upload time: 2024/11/8

Payment Methods

All payment methods are secure and covered by SeekIC Buyer Protection PLUS.

Notice: When you place an order, your payment is made to SeekIC and not to your seller. SeekIC only pays the seller after confirming you have received your order. We will also never share your payment details with your seller.
Product Details

Description



Features:

• TRMS active power relays for three phase balanced applications
• Measuring if active power is within set limits
• Measuring voltage on own power supply
• Measuring ranges: 5A, 10A, MI current transformers
• Power ON delay 1 to 30 s knob selectable
• Separately adjustable upper/lower level on relative scale
• Programmable latching or inhibit at set level
• Automatic and manual start and stop of the system
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN
   50 022 (DWB02) or plug-in module (PWB02)
• 45 mm Euronorm housing (DWB02) or 36 mm plug-in module (PWB02)
• LED indication for relay, alarm and power supply ON



Description

DWB02 and PWB02 are precise TRMS active power monitoring relays for 3- phase balanced systems. They can be used for monitoring the actual load of asynchronous motors and other symmetrical loads, as well as the power consumption by of system.

Start/stop input PWB02 allows to use a manual switch to start and stop the system, without the need of an auxiliary device.

The advantage of using the latch function is that the alarm status can be kept even after the end of the alarm condition. Inhibit function can be used to avoid relay operation when not desired (maintenance, transitions).

The LED's indicate the state of the alarm and the output relay.