Features: ·CALIBRATION CAPABILITY·INTEGRAL SENSOR EXCITATION·OPEN CIRCUIT SENSOR DETECTION·LOW POWER: 80mW·INSTRUMENT AMPLIFIER INPUT·PROGRAMMABLE GAIN·12-BIT LINEARITY·TWO ISOLATED POWER SUPPLIES:±13V at 5mA·LOW DRIFT 10V REFERENCEApplication·UNIVERSAL INPUT CHANNEL FOR PROCESS CONTROL SYSTEMS·IS...
ISC300: Features: ·CALIBRATION CAPABILITY·INTEGRAL SENSOR EXCITATION·OPEN CIRCUIT SENSOR DETECTION·LOW POWER: 80mW·INSTRUMENT AMPLIFIER INPUT·PROGRAMMABLE GAIN·12-BIT LINEARITY·TWO ISOLATED POWER SUPPLIES:±...
SeekIC Buyer Protection PLUS - newly updated for 2013!
268 Transactions
All payment methods are secure and covered by SeekIC Buyer Protection PLUS.
·UNIVERSAL INPUT CHANNEL FOR PROCESS CONTROL SYSTEMS
·ISOLATED MEASUREMENT CHANNEL FOR THERMOCOUPLE, RTD AND VOLTAGE TRANSDUCERS
·CHANNEL TO CHANNEL ISOLATED MULTIPLEXED SYSTEMS
·ISOLATED 4 TO 20mA RECEIVER
Signal Input Voltage ........................................................................±380V
Analog Supply Voltage VCC ..................................................................18V
Digital Supply Voltage VDD .................................................................... 7V
Voltage Across Barrier ................................................................. 800Vrms
Storage Temperature Range .......................................... 45 to +100
Lead Temperature (soldering, 10s) ................................................ +300
Out Short Circuit Duration ........................................ Continuous to Com 2
Relative Humidity (non-condensing) ............................................. 95% RH
NOTES: Stresses exceeding those listed above may cause permanent damage to the device. Exposure to absolute maximum rating conditions for extended periods may affect device reliability.
The ISC300 is an isolated measurement channel with open circuit sensor detection for use with RTD and thermocouple temperature sensors. In addition to temperature measurement, the ISC300 can accept full scale input voltages of ±100mV and ±10V which allows use with other sensors such as pressure, humidity and flow sensors. The low level resistance measurement capability also allows stimulus and measurement of strain gauges. The measurement channel has a highly stable internal reference which can be selected from the output side. This allows the user to calibrate each channel at the factory, record the calibration data and periodically recalibrate the system while in use over time and ambient temperature changes.